Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Still deciding? Get samples of US$ 9500/Set
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Wahbou RM06 30kVA-150kVA Modular UPS Double Conversion Online UPS with Digital Control System
Model | RM30 90 | RM30 150 | RM30 300 | ||
Capacity | UPS Cabinet | 30-90kW | 30-150kW | 30-300kW | |
Power Module | 30kW | ||||
Input | Input Form | 3P4W+G | |||
Rated Voltage | 380/400/415 Vac | ||||
Voltage Range | 207-478Vac | ||||
Frequency Range | 40-70Hz | ||||
Input Power Factor | ≥0.99 | ||||
Bypass Range | 380 upper limit: 25% (optional +10%,+15%,+20% ) 400 upper limit: 20%(optional+10%,+15%) 415 upper limit: 15%(optional+10%) Lower limit: -45% (optional -20%,-30%) Bypass frequency protection range: ± 10% |
||||
Input Current Harmonic Wave | ≤3% (100% non-linear) | ||||
Output | Output Form | 3P4W+G | |||
Rated Voltage | 380/400/415 Vac | ||||
Output Power Factor | 0.9 or 1 | ||||
Voltage Accuracy | ±1% | ||||
Output Frequency | Mains Mode | Synchronization with input; when mains frequency exceeds maximum value ±10% (can be set ±1%,±2%,±4%,±5%), output frequency 50X(±0.2%)Hz | |||
Battery Mode | (50/60±0.2%) Hz | ||||
Crest Factor | 3:1 | ||||
Conversion Time | Mains mode → bypass mode : 0ms (tracking) ; Mains mode→ battery mode: 0ms | ||||
Overload Capacity | Load≤110%: 60 mins; Load≤125%: 10 mins; Load≤150%: 1 min; Load≥ 150%, shutdown immediately | ||||
Output Voltage Harmonic Wave | ≤ 2% (100% linear) | ||||
Efficiency | In normal mode 95% | ||||
Communication Port | RS232,RS485,Intelligent Slot*2 ,Dry connect port | ||||
Battery | Battery Voltage | ±192Vdc/±204Vdc/±216Vdc/±228Vdc/±240Vdc; (32/34/36/38/40pcs of battery to select) | |||
Charging Current | UPS Cabinet | 30A Max | 50A Max | 100A Max | |
Power Module | 10A Max | ||||
Environment | Operating Temperature | 0ºC-40ºC | |||
Relative Humidity | 0-95% (non-condensing) | ||||
Storage Temperature | -25-55ºC ( excluded battery) | ||||
Altitude | <1500m (derating if exceeding 1500m) | ||||
Physical Characteristic | Dimension (LxWxH) mm | Cabinet | 840x600x1400 | 1100x600x2000 | |
Module | 580x443x131 | ||||
Net Weight(kg) | Cabinet | 158 | 170 | 305 | |
Module | 30K module: 33.5kgs | ||||
Operative Standard | YD/T 2165-2010 |