Customization: | Available |
---|---|
Phase: | Three Phase |
Type: | On-line |
Still deciding? Get samples of US$ 1599/Set
Order Sample
|
Shipping Cost: | Contact the supplier about freight and estimated delivery time. |
---|
Payment Methods: |
|
---|---|
Support payments in USD |
Secure payments: | Every payment you make on Made-in-China.com is protected by the platform. |
---|
Refund policy: | Claim a refund if your order doesn't ship, is missing, or arrives with product issues. |
---|
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Three Phase 380VAC PT02 40kVA Online UPS High Frequency Power Supply
Model | VT33 10KVA | VT33 10KS | VT33 20KVA | VT33 20KS | VT33 30KS | VT33 40KS | |
Rated Power | 10kVA/9kW | 20kVA/18kW | 30kVA/27kW | 40kVA/36kW | |||
Input | Voltage Range | 207-475Vac 3P4W+G | |||||
Working Frequency Range | 40-70Hz (settable) | ||||||
Input Power Factor | ≥0.99 | ||||||
Output | Rated Voltage and Accuracy | 380Vac(1±1%) 3P4W+G | |||||
Output Frequency | 46-54Hz synchronize with mains power; 50Hz (Mains power between 40-46Hz and 54-60Hz ); 50Hz(Battery) | ||||||
Rated Current | 15A | 30A | 45A | 61A | |||
Output Power Factor | 0.9 | ||||||
Output Harmonic Wave | ≤3% (Full R load) | ||||||
Crest Factor | 3: | 1 | |||||
Output Overload | 105%±5%<Load≤125%±5%: Convert to bypass output and alarm after 1min; 125%±5%<Load≤150%±5%: Convert to bypass output and alarm after 30s; Load>150%±5%: Convert to bypass output and alarm after 300ms. |
||||||
Conversion time between Mains Power and Battery | 0ms | ||||||
Efficiency | >92% | >91% | |||||
Battery | Rated Voltage | 192Vdc | ±192Vdc | ||||
Quantity | 16 | 32 | |||||
Charging Current | 1A | 5.5A | 1A | 7.5A | 5.5A | ||
Dimension (LxWxH) mm | 560x260x717 | 533x260x501 | 710x260x717 | 710x260x717 | |||
Weight | 72kg | 26kg | 98kg | 57.5kg | 58.5kg | 62kg | |
Working Temperature | 0ºC-40ºC | ||||||
Working Humidity | 20%-95% (non-condensing) | ||||||
Noise | ≤60dB |